Madison, WI Header
Meeting Name: BUILDING CODE, FIRE CODE, CONVEYANCE CODE AND LICENSING APPEALS BOARD Agenda status: Approved
Meeting date/time: 6/7/2016 12:15 PM Minutes status: Approved  
Meeting location: 215 Martin Luther King, Jr. Blvd. Room LL-110 (Madison Municipal Building)
Published agenda: Agenda Agenda Published minutes: Minutes Minutes  
Agenda packet: Not available
Meeting video:  
Attachments:
File #Ver.Agenda #Boards, Commissions and CommitteesTypeTitleActionResultAction DetailsWatch
43280 11810 East WashingtonMiscellaneous810 East Washington (C-06-33-2016) Christopher Gosch of Bark Design appealing IBC section 3007.1. The rule requires that a fire service elevator serve all levels in a structure. The variance requested is to allow the elevator to serve the floor below the highest floor. Additional means of safety have been provided. The variance is supported by the Madison Fire Department.Approve  Action details Not available
43270 12433 W JohnsonMiscellaneous433 W Johnson (C-06-34-2016) John Sutton of Sutton Architecture appealing IBC 3007.4. The proposal is to use the 2015 IBC. The existing elevators are not fire service elevators. The two elevators will be converted to fire service elevators and lobbies created. The mechanical parking ramp below grade will be served by a pressurized stairwell. The Madison Fire Department supports the variance with the following conditions: -Construct 160-square foot elevator lobbies. -Install 45-minute rated doors for all doors opening into corridors as permitted in the 2015 edition of the IBC. -Add stair pressurization to Stair C. -Meet all other requirements of IBC 3007, hoistway lighting, electrical power, and protection of wiring & cables. -Construct elevator lobbies on each floor that comply with the required fire openings. -Update plans in the Fire Command Center. -Update the smoke control panel to include the stair pressurization for Stair C.Approve  Action details Not available