File #: 95701    Version: 1 Name: Data Center Ordinance
Type: Ordinance Status: Council New Business
File created: 11/18/2026 In control: Attorney's Office
On agenda: 11/24/2026 Final action:
Enactment date: Enactment #:
Title: Amending several sections of Chapter 28 of the Madison General Ordinances related to the definition of data centers and the regulation of data centers under 75,000 square feet in floor area to be an allowable use in a limited number of non-residential zoning districts and repealing Section 28.140 of the Madison General Ordinances, the temporary data center moratorium.
Sponsors: Satya V. Rhodes-Conway, Derek Field, John P. Guequierre
Attachments: 1. 95701Body.pdf, 2. Data Center Code Amendment Memo 11-19-26.pdf

Fiscal Note

[Enter Fiscal Note Here]

Title

Amending several sections of Chapter 28 of the Madison General Ordinances related to the definition of data centers and the regulation of data centers under 75,000 square feet in floor area to be an allowable use in a limited number of non-residential zoning districts and repealing Section 28.140 of the Madison General Ordinances, the temporary data center moratorium.

Body

DRAFTER’S ANALYSIS: This proposed ordinance amends, repeals and creates multiple sections of Madison’s zoning code, MGO Chapter 28, to create a regulatory framework on data centers. Currently, the City of Madison has a data center moratorium (MGO Sec. 28.140) in effect to allow City of Madison agencies and policymakers to research and propose regulations. Prior to the moratorium, the zoning code did not have a definition or specific standards for ‘Data Centers’ as a use category and generally categorized the previously existing data centers as ‘Telecommunications Centers,’ an outdated term.

First, MGO 28.140 is repealed. A new use ‘Data Center’ is added to the code and defined in MGO Sec. 28.211 as “an establishment that is up to 75,000 square feet of floor area that is used for the storage, management, processing, and transmission of digital data, which houses computer or network equipment, systems, servers, appliances and other associated components related to digital data operations.” Data centers are distinguished from ‘Server Rooms,’ which are newly defined in the zoning code. Server rooms are “one or more designated areas within a portion of a building containing a principal use other than a data center that houses computer and network equipment, systems, servers, appliances, and other associated hardware components related to its digital data operations.” The ‘Telecommunications Center’ definition is also updated to distinguish it from both data centers and server rooms.

Data centers larger than 75,000 square feet in floor area are not allowed in the City of Madison. Data centers 75,000 square feet in floor area or less will be allowed as a permitted use in a limited number of non-residential districts with Supplemental Regulations that are specific to the potential impacts associated with the data center size. Data centers less than 10,000 square feet in floor area are permitted in the Mixed-Use and Commercial districts, Downtown and Urban districts, Employment districts, the Airport (AP) district, and the Campus Institutional (CI) district. Data centers between 10,000 square feet and up to 50,000 square feet in floor area will be allowed in the Employment districts (except the Traditional Employment (TE) district) and in the Campus Institutional (CI) district. Data centers between 50,000 square feet and 75,000 square feet in floor area will only be allowed in the Industrial Limited (IL), Industrial General (IG), and Airport (AP) districts. Data centers of greater than 10,000 square feet in floor area are prohibited in the Transit Oriented Development (TOD) Overlay District. Data centers are not permitted in Residential districts.

Planned Development (PD) districts may allow a data center if there is an equivalent zoning district which allows data centers identified in the PD’s zoning text, or the property is rezoned to a zoning district that would allow one. Planned Development districts shall not be used to alter the Supplemental Regulations for data centers under MGO 28.151 or allow data centers larger than 75,000 square feet in floor area.

All data centers would be subject to the Supplemental Regulations under MGO 28.151. The proposed supplemental regulations are targeted zoning regulations recommended to mitigate potential anticipated impacts from data centers based on their size. Data centers are prohibited at the ground level of a building except in the IL, IG, AP and CI districts. A data center building larger than 10,000 square feet in floor area shall not be located within 1,000 feet of the boundary of any parcel occupied by another data center larger than 10,000 square feet in floor area.

For data centers larger than 10,000 square feet, mechanical equipment and emergency generators shall be surrounded by a solid wall on all sides. Data centers over 10,000 square feet shall provide a Noise Mitigation Plan that demonstrates compliance with the noise ordinance, MGO Sec. 24.08. MGO Sec. 24.08 already regulates excessive noise in the City of Madison, including mechanical and construction-related equipment, and determines the maximum dBA by zoning district.

The Supplemental Regulations also include buffers for data centers larger than 50,000 square feet and any associated ground mounted mechanical equipment and emergency generators. A buffer of at least three hundred (300) feet is required from properties that are in the DC, UOR, UMX, TE, SE, SEC, EC, A, UA, CN, PR, CI, and MC districts, and from Planned Development districts that do not allow residential uses. A buffer of at least five hundred (500) feet is required from properties in Residential districts, Mixed-Use and Commercial districts, the Planned Mobile Home Park district, and from Planned Development districts that allow residential uses. No buffer is required from properties that are in the IL, IG, ME, or AP districts.

***********************************************************************************                     

 

Please see Legistar File No. 95701 Body in Attachments.